Service manual
Installation Instructions Section 2
2-6
Part No. 80-1206-3
Location of CVD Condensing Unit
The location selected for the CVD Condensing Unit must
meet the following criteria. If any of these criteria are not
met, select another location.
• The air temperature must be at least -20°F (-28.9°C)
but must not exceed 130°F (54.4°C).
• CVD1476 Only - The air temperature must be at
least 50°F (10°C) but must not exceed 110°F (43°C).
• CVD1875/CVD2075 Only - The air temperature must
be at least -20°F (-28.9°C) but must not exceed
120°F (48.9°C).
• The location must not allow exhaust fan heat and/or
grease to enter the condenser.
• The location must not obstruct airflow through or
around the condensing unit. Refer to the chart below
for clearance requirements.
Condensing Unit Clearance Requirements
Top/Sides
There is no minimum clearance required, although 6”
(152 mm) is recommended for efficient operation and
servicing only.,
Front/Back
48” (122 cm)
CVD1476 ONLY
Top - 5” (127 mm) is recommended for efficient
operation and servicing only.
Front/Back/Sides - 12” (305 mm)
Condensing Unit Heat of Rejection
QuietQube® ice machine head sections add an
insignificant amount of load to a conditioned space.
Series
Condensing Unit
Heat of Rejection*
B.T.U./Hour
Air Conditioning**
Because the heat of rejection varies during the ice making cycle,
the figure shown is an average.
Peak
CVD675 9,000 13,900
CVD875 12,400 19,500
CVD1075 16,000 24,700
CVD1285 19,000 28,000
CVD1475 24,000 35,500
CVD1476 24,000 35,500
CVD1875 28,000 42,000
CVD2075 39,000 53,000