Service manual

Refrigeration System Section 7
7-14
Part No. 80-1206-3
Safety Limit #2
Control Board with Black Microprocessor - Harvest time exceeds 3.5 minutes for 3 consecutive harvest cycles.
or
Control Board with Orange Label on Microprocessor - Harvest time exceeds 3.5 minutes for 500 consecutive
harvest cycles.
QDUALC ONLY - Harvest cycle time exceeds 7 minutes for 3 consecutive harvest cycles.
SAFETY LIMIT NOTES
Because there are many possible external problems,
do not limit your diagnosis to only the items listed in
this chart.
A continuous run of 100 harvests automatically
erases the safety limit code.
The control board will store and indicate only one
safety limit – the last one exceeded.
If the toggle switch is moved to the OFF position and
then back to the ICE position prior to reaching the
100-harvest point, the last safety limit exceeded will
be indicated.
If the harvest light did not flash prior to the ice
machine restarting, then the ice machine did not stop
because it exceeded a safety limit.
SAFETY LIMIT STAND-BY MODE
(QDUAL ONLY)
The first time a safety limit shut down occurs, the ice
machine turns off for 60 minutes (Stand By Mode). The
ice machine will then automatically restart to see if the
problem re-occurs. During the Stand By Mode the
harvest light will be flashing continuously and a safety
limit indication can be viewed. If the same safety limit is
reached a second time (the problem has re-occurred 3
more consecutive time) the ice machine will initiate a
safety limit shut down and remain off until it is manually
restarted. During a safety limit shut down the harvest
light will be flashing continuously.
Possible Cause Check/Correct
Improper installation
See “Installation/Visual Inspection Checklist”
Water system Water area (evaporator) dirty
Dirty/defective water dump valve
Vent tube not installed on water outlet drain
Water freezing behind evaporator
Plastic extrusions and gaskets not securely mounted to the
evaporator
Dirty/defective float valve (Q1400C Only)
Electrical system Ice thickness probe out of adjustment (premature harvest)
Ice thickness probe dirty
Bin switch defective
Refrigeration system Non-Manitowoc components
Improper (low or overcharge) refrigerant charge
Defective head pressure control valve
Defective cool vapor valve
Defective fan cycling control (CVD0675/CVD1476 do not have
a fan cycle control)
CVD1476 Only - Water inlet valve is incorrectly adjusted or will
not close during harvest cycle.