Specifications

Part Number 000001528 2-1
Section 2
Installation Instructions
General
These instructions are provided to assist the qualified
installer. Check your local Yellow Pages for the name of
the nearest Manitowoc distributor, or call Manitowoc Ice,
Inc. for information regarding installation and start-up
services.
Ice Machine Installation Options
CVD1476 CONDENSER WATER PRESSURE
Water pressure at the condenser cannot exceed 150
psig (1034 kPA) with the standard water-regulating
valve. Contact your distributor if your water pressure is
greater than 150 psig (1034 kPA). A special order
condensing unit is available that allows water pressure
up to 350 psig (2413 kPA).
Q1400C HEAD SECTION
The ice machine head can be installed with the electrical
inlet, water supply inlet and refrigeration tubing entering
from the back or top of the ice machine.
The ice machine water drain must exit the back of the
ice machine.
Cut the top cover for top routing of electrical inlet, water
supply inlet or refrigeration lines.
1. Prior to cutting, mount top cover onto ice machine.
2. Locate the area that will need to be cut and mark the
top cover.
3. Using a tin snips, cut top cover as needed:
A. Do not cut out entire area! Cut up to 1/8 inch to
marked line.
B. Cut out only what is needed. (If routing only
refrigeration lines out the top, cut just enough to
route these lines.)
Do not cut out the entire corner area.
Important
Failure to follow these installation guidelines may
affect warranty coverage.
TUBING CAN BE
ROUTED OUT TOP
SV1769A
TUBING CAN BE
ROUTED OUT
BACK OF THE ICE
MACHINE WITH
PROVIDED 90
°
ELL’S
TRIM TOP COVER
IN THIS AREA
SV1768B