Service Manual
Table Of Contents
- General Information
- Model Numbers
- Installation
- Maintenance
- Troubleshooting
- Component Check Procedures
- Electrical Components
- Main Fuse
- ICE/OFF/CLEAN Toggle Switch
- Float Switch
- Ice Damper and Hall Effect Switches
- Selector Switch
- Dispense Lever Activated
- Touchless Sensor Activated
- Dispense Switch
- Touchless Sensor
- High Pressure Cutout Control
- Fan Cycle Control
- Low Pressure Cutout (LPCO) Control
- Compressor Electrical Diagnostics
- Diagnosing Start Components
- Refrigerant Recovery/Evacuation
- System Contamination Clean-Up
- Electrical Components
- Component Specifications
- Charts
- Diagrams
Part Number 000015432 4/18 95
CLEANUP PROCEDURE
Mild System Contamination
1. Replace any failed components.
2. If the compressor is good, change the oil.
3. Replace the liquid line drier.
NOTE: If the contamination is from moisture, use heat
lamps during evacuation. Position them at the compressor,
condenser and evaporator prior to evacuation. Do not
position heat lamps too close to plastic components, or
they may melt or warp.
Important
Dry nitrogen is recommended for this procedure. This
will prevent refrigeration release.
4. Follow the normal evacuation procedure, except
replace the evacuation step with the following:
A. Pull vacuum to 1000 microns. Break the vacuum
with dry nitrogen and sweep the system.
Pressurize to a minimum of 5 psig (35 kPa,
.35 bar).
B. Pull vacuum to 500 microns. Break the vacuum
with dry nitrogen and sweep the system.
Pressurize to a minimum of 5 psig (35 kPa,
.35 bar).
C. Change the vacuum pump oil.
D. Pull vacuum to 500 microns. Run the vacuum
pump for 1/2 hour on self-contained models,
1 hour on remotes.
NOTE: You may perform a standing vacuum test to make a
preliminary leak check. You should use an electronic leak
detector after system charging to be sure there are no
leaks.
5. Charge the system with the proper refrigerant to the
nameplate charge.
6. Operate the ice machine.