Will Not Stop Dispensing
• Disconnect sensor plug from sensor control board.
• If the dispensing stops, replace the sensor
• If the dispensing continues, disconnect wires #59
& #60 from the control board
• Check resistance across control board contacts
• Closed = Replace the touchless sensing control
board
• Open = Dispense control board is not functioning
correctly, check control board relays
Replace the selector switch if ohm readings do not match
all three switch settings.