Manual

Mammoth V-Cube Slim IOM, MAMM-VCS-IOM-4FA (October 2013) 16
Electrical Terminal Tightening Torques
The following tables provide tightening torques, as rec-
ommended by the component manufacturer, for many of
the electrical components provided on Mammoth units.
If a torque value is provided on the component, use that
value instead. Where no torque value is given or provided
here, use the torques provided in the tables at the end of
this section, which are taken from UL Standard 486A.
Table 3: Telemecanique manual motor starters, controllers, and protectors
Device Model Tightening Torque
Motor Starter GV2ME 15 lb-in (1.7 N•m)
Motor Starter GV2P 15 lb-in (1.7 N•m)
Motor Starter LS1D30, LS1D303 15 lb-in (1.7 N•m)
Motor Starter LS1D32, LS1DT32, LS1D323 15 lb-in (1.7 N•m)
Motor Starter GV3ME06 through ME20 15 lb-in (1.7 N•m)
Motor Starter GV3ME25 through ME63 44 lb-in (5 N•m)
Trip Module GV2AU 12 lb-in (1.4 N•m) max
Trip Module GV2AS 12 lb-in (1.4 N•m) max
Auxiliary Contact GVAN, GVAD 12 lb-in (1.4 N•m) max
Auxiliary Contact GV2AD, GV2 AM11 12 lb-in (1.4 N•m) max
Auxiliary Contact GV2AE 12 lb-in (1.4 N•m) max
Terminal Block GV2G05 and GV1G09 Connector: 20 lb-in (2.2 N•m)
Screw clamp: 15 lb-in (1.7 N•m)
Table 4: Altivar 212 variable speed drives
Maximum Wire Size Tightening Torque
mm
2
AWG N-m lb-in
6 10 1.3 11.5
16 6 2.5 22
25 3 4.5 40
50 1/0 24 212
150 300 kcmils 41 363