Owner manual

17
MAMM-WSHP-IOM-1MA
Examples of I/O’s
INPUTS
Point Description
UD #1
+Pulse
BMS Supply Air, Duct Static Reset or Room Air Temperature Setpoint
UD #2
Room Air Temperature
UD #3
RTD/Therm/Dry
System Switch Emergency Shut Down Remote Start
UD #4 Contact, 0-10VDC,
High Static Low Static VFD in Bypass
UD #5 0-20MA
Economizer Lockout Cooling Lockout Heating Lockout
UD #6

Supply Fan Status Compressor Fault Condensate Overflow
UD #7

Duct Static Pressure or Airflow Switch
UD #8

Filter Static Pressure or Dirty Filter Switch #1
UD #9

Outside Air Temperature (AiSE Only)
UD #10

Condenser Water Temperature
UD #11
 Entering Air Temperature or Return Air Temperature (AiSE)
UD #12

Supply Air Temperature
OUTPUTS
Point Description
UO #1
4-20mA, 0-10Vdc
Spare
UO #2
Heating Source Control Signal
UO #3
0-10 Vdc
Economizer Valve (WiSE)/Damper Control Signal (AiSE)
UO #4
WiSE Bypass Valve Signal
UO #5
Spare
UO#6
Supply Fan VFD Control Signal
DO #1
120 VAC
Start Supply Fan
DO #2
FORM C
Start Condenser Pump or Switch Reversing Valve
DO #3
 Field-Lin (MWU or Open Min OA)
DO #4
 Common Alarm
DO #5
 Compressor Call #2
DO #6

Compressor Call #1