Hearth & Home Technologies • Power Vent Inline (PVI-SLP) Instructions • 2196-900 Rev. AC • 12/15
Top Vent - Vertical Termination - (continued)
V
3
V
2
V
1
H
1
H
2
A DVP-2SL ADAPTER
is required in this position
in the vent run on certain
models. See Table 2.1.
WARNING! Risk of Overheating!
- Minimum inital length of vent pipe required between
appliance and vertically positioned PVI-SLP.
- Must include two 90 degree elbows.
Figure 2.6 Vertical PVI-SLP Orientation
Minimum Maximum
H
1
+ V
1
+ V
2
24 in. 610 mm See Chart in Section 2.C: "Venting Length - Model
Categories and Length Requirements by Termina-
tion Type."
V
3
18 in. 457 mm See Chart in Section 2.C: "Venting Length - Model
Categories and Length Requirements by Termina-
tion Type."
H
TOTAL
0 in. 0 in. 30% of total vent length allowed in chart: "Venting
Length - Model Categories and Length Require-
ments by Termination Type" in Section 2.C.
A minimum of 2ft. of vertical piping is required between the appliance and the PVI-
SLP in addition to the minimum venting described above when installing PVI-SLP with
certain appliance models. See Table 2.1.
V minimum = 2 ft. and v2 + H1 + V1 minimum = 4 ft. for certain appliance models. See
Table 2.1.
WARNING! Risk of Fire! Use DVP pipe between appliance and PVI-SLP
on these models:
ESCAPE-42DV, ESCAPE-36DV, ESC-42ST, HEIR36, HEIR42, HEIR50,
LUX36, LUX42, TRUE-36, TRUE-42, TRUE-50, CERONA-36, CE-
RONA-42, MEZZO36, MEZZO36ST, CRAVE4836, CRAVE4836ST,
MEZZO48, MEZZO48ST, CRAVE6048, CRAVE6048ST, MEZZO60,
MEZZO60ST, CRAVE7260, CRAVE7260ST, MEZZO72, MEZZO72ST,
CRAVE8472, CRAVE8472ST
Combustibles surrounding pipe may overheat.
Note: For PRIMO models, see the PRIMO Installation Manual for vent
confi gurations.