Installation Manuel
8
Hearth & Home Technologies • Power Vent Inline (PVI-SLP) Instructions • 2196-900 Rev. AC • 12/15
Top Vent - Vertical Termination
H
1
V
2
V
1
H
2
A DVP-2SL ADAPTER
is required in this position
in the vent run on certain
models. See Table 2.1.
Figure 2.5 Horizontal PVI-SLP Orientation
Minimum Maximum
H
1
+ V
1
24 in. 610 mm See Chart in Section 2.C: "Venting Length - Model Categories and Length
Requirements by Termination Type."
V
2
18 in. 457 mm See Chart in Section 2.C: "Venting Length - Model Categories and Length
Requirements by Termination Type."
H
TOTAL
00
30% of total vent length allowed in chart: "Venting Length - Model Categories
and Length Requirements by Termination Type" in Section 2.C.
A minimum of 2ft. of vertical piping is required between the appliance and the PVI-SLP in addition to the
minimum venting described above when installing PVI-SLP with certain appliance models. See Table 2.1.
V minimum = 2 ft. and H
1
+ V
1
minimum = 4 ft. with certain appliance models. See Table 2.1.
Note: 1 ft. of vertical drop decreases
total allowable length by 2 ft.
WARNING! Risk of Fire! Use DVP pipe between appliance and PVI-SLP on these models:
ESCAPE-42DV, ESCAPE-36DV, ESC-42ST, HEIR36, HEIR42, HEIR50, LUX36, LUX42,
TRUE-36, TRUE-42, TRUE-50, CERONA-36, CERONA-42, MEZZO36, MEZZO36ST,
CRAVE4836, CRAVE4836ST, MEZZO48, MEZZO48ST, CRAVE6048, CRAVE6048ST,
MEZZO60, MEZZO60ST, CRAVE7260, CRAVE7260ST, MEZZO72, MEZZO72ST,
CRAVE8472, CRAVE8472ST
Combustibles surrounding pipe may overheat.
Note: For PRIMO models, see the PRIMO Installation Manual for vent confi gurations.