Installation Manuel

4
Hearth & Home Technologies • Power Vent Inline (PVI-SLP) Instructions • 2196-900 Rev. AC • 12/15
Table 2.1
WARNING! Risk of Fire!
PVI-SLP cannot be installed directly on appliance. The PVI-SLP and combustible materials surrounding vent pipe may
overheat.
A minimum length run of initial vent pipe is required between the appliance and the inlet of the PVI-SLP. The initial
minimum vent run requirement varies depending on the speci c appliance and its venting con guration.
Some models require DVP Series pipe for the initial minimum vent section directly off the appliance.
MODEL MINIMUM VENTING BETWEEN APPLIANCE AND PVI-SLP
6000C, 6000CL, 6000CLX,
8000C, 8000CL, 8000CLX 6000BEC
PVI installed horizontal orientation: One 90 degree elbow and
a total of two feet of straight horizontal or straight vertical SLP
pipe. See Figure 2.2 and Figure 2.5.
PVI installed vertical orientation: Two 90 degree elbows and
a total of two feet straight horizontal or straight vertical SLP pipe.
See Figure 2.3, 2.4, 2.6.
6000CMOD, 8000CMOD
CD4236, CD4842
CNXT4236, CNXT4842
CRAVE4836, CRAVE4836ST, CRAVE6048, CRAVE6048ST
CRAVE7260, CRAVE7260ST, CRAVE8472, CRAVE8472ST
DV3732SBI
GDST3831, GDST4336, GDFL4136, GDCR4136,
GDCL4136
MEZZO36, MEZZO36ST, MEZZO48, MEZZO48ST
MEZZO60, MEZZO60ST, MEZZO72, MEZZO72ST
NDV3630, NDV3933, NDV4236, NDV4842
NEVO3630, NEVO4236
ST-36TR. ST-36TR, ST-36TRB, PIERI-36TR, PIER-36TRB,
LCOR-36TRB, RCOR-36TRB
RED40, RED40ST
REVO-S21, REVO-H31
SLR32, RAVE3012I
SLR-B, SLR-C,
RAVE 4013I, RAVE4013I-C
SL-350TRS, SL-550TRS, SL-750STRS
SL-550TR, SL-750TR, SL-950TR
SL-550METRO, SL-550-BE-M
ST-550T, ST-550TM
MODEL MINIMUM VENTING BETWEEN APPLIANCE AND PVI-SLP
ESC-42ST
PVI installed horizontal orientation: Minimum two feet straight
vertical DVP pipe directly off appliance followed by 90 degree
elbow and two feet DVP pipe. PVI-SLP adapter must be located
directly between initial DVP pipe and PVI-SLP. See Figure 2.2
and Figure 2.5.
PVI installed vertical orientation: Minimum two feet straight
vertical DVP pipe directly off appliance, followed by two 90
degree elbows and a total of two feet straight horizontal or
straight vertical DVP pipe. PVI-SLP adapter must be located
directly between initial DVP pipe and PVI-SLP. See Figure 2.3,
Figure 2.4, Figure 2.6.
ESCAPE-36DV, ESCAPE42DV
HEIR36, HEIR42, HEIR50
LUX36, LUX42
TRUE-36, TRUE-42, TRUE-50
CERONA-36, CERONA-42
PRIMO48, PRIMO48ST, PRIMO60, PRIMO60ST,
PRIMO72, PRIMO72ST
PVI installed vertical or horizontal orientation: Minimum three
feet of DVP or SLP pipe is required before connecting the PVI-
SLP system. The 3 foot minimum does not include the factory-
installed six inch DVP pipe.
B. Vent/Pipe Regulations (continued)