Installation Manuel

22
Hearth & Home Technologies • Power Vent Inline (PVI-SLP) Instructions • 2196-900 Rev. AC • 12/15
A. Installation Inspection
1. Follow safety inspection procedures recommended by
national, provincial, and/or local codes.
2. Be certain all electrical connections are properly made
and secure.
3. Visually inspect the vent system and determine that
there is no ue gas spillage, blockage or restriction,
leakage, corrosion or other unsafe de ciencies.
4. Place the replace in operation and determine that the
burner and power vent are operating properly. The
main burner should show no signs of oating, lifting, or
ashbacks.
B. Vacuum Switch Orientation
The vacuum switch must be installed on a vertical plane
for proper function. If the PVI-SLP is mounted in a vertical
position, the vacuum switch needs to be moved from its
place in Figure 5.1 to the location shown in Figure 5.2. To
do this, loosen and remove the two nuts securing it to the
inside wall of the PVI-SLP. Move and secure the vacuum
switch onto the adjacent wall using the two bolts that are
sticking out of the surface. Be sure that the tube running
from the vacuum switch to the motor is not pinched closed.
5
5
Operating Instructions
C. Setting the PVI-SLP Baf e Adjustment
The PVI-SLP has a baf e adjustment which must be set
during the Installation Inspection. This baf e adjustment
is located alongside the motor. See Figure 5.3.
The baf e adjustment is measured using the holes on the
indicator bar of the PVI-SLP baf e. See Figure 5.4. This
bar raises as the baf e is opened and lowers as the baf e
is closed. When only one hole is showing, the baf e is
closed. When all three holes are visible, the baf e is all
the way open. DO NOT TRY TO FORCE IT OPEN ANY
FURTHER THAN 1/2 in.
When the power vent is located within ten feet of the ap-
pliance, there is no limit to the baf e adjustment. If the
power vent is located more than 40 feet from the appliance,
the ue baf e must remain closed and cannot be adjusted.
See Table 3 for limitations to the baf e adjustment.
The need to adjust the baf e will depend upon vent run
con guration and burner ame characteristics.
Next to the bolt used for baf e adjustment is an indicator bar.
If the burner ames are short, active, and jumping – turn
the bolt clockwise (open). Check the burner ames and
adjust the baf e again as necessary until the ames are
stable, strong, and steady.
If the burner ames are tall, lifting, oating, and ghost-
like, the baf e is too open and MUST be closed (turn bolt
counter-clockwise).
If the pilot continously sparks and does not become
steady, the baffle may need to be opened. The
requirements in table 3 must still be met.
Figure 5.1 Switch Position for Horizontal Installation
Figure 5.2 Switch Position for Vertical Installation
CAUTION! Risk of electrical shock! DO NOT allow
120VAC wires to contact hot metal surfaces. Use sup-
plied wire ties to bundle wires away from ue pipe, fan
housing and other metal surfaces.
ZIP TIE
ZIP TIE
CAUTION! Risk of overheating! The baf e must re-
main fully closed when using the PVI-SLP with the PRI-
MO models. See PRIMO Installation Manual for details
and PRIMO48/PRIMO48ST exception.
PRIMO MODELS ONLY: