User Manual

8
PH Gas Logs
65D2035
and 
The sides of the re-
place opening must be at least 16" from any combustible
wall. The ceiling must be at least 42" from the top of the
replace opening.


   minimum clearances   




Follow these instructions carefully to ensure safe installation. Failure to
follow instructions exactly can create a re hazard.
16"
42"
FP1996
wall ceiling clearances
Figure 3 -
Sidewall and Ceiling Clearances
FP1996



To install the gas logs into a replace with no wooden
mantel, shelf or other combustible projection above the
replace opening, measure the heat resistant material
height, per Figure 4, then see TABLE A.
Heat resistant materials such as slate and marble must 


IMPORTANT: If you cannot meet these minimum clear-
ances you must operate the heater with chimney ue
damper open. Refer to "Installing Vented Applications"
found on Page 14.
FP2922
heat resist material
Heat
Resistant
Material
Measure This
Distance
Heater in
Fireplace or
Firebox
FP2922
Figure 4 -
Measure Heat Resistant Material
Table A -
Heat Resistant Material Requirements with No
Mantel or Combustible Projection
 
 
12" or more Hood not required
8" or less than 12" Extend resistant material to
12" or install hood. Figure 5
Less than 8" Extend heat resistant material
to at least 8" and install hood.
Figure 5. , extend heat
resistant material to a height
of at least 12"