Decorative Shroud Install Manual

Hearth & Home Technologies Inc. • LDS33/LDS46 Decorative Shrouds • 31173 • Rev E • 04/09
2
WARNING! Risk of Fire!
You must maintain clearances to
avoid overheating the chase structure.
The TR Series cap must be raised to the minimum
dimensions (or greater) above the shroud as shown in
Figure 6.
A. Make sure the shroud will meet or exceed the minimum requirements for the termination cap you are going
to install as shown in Figures 4-6.
16 in. (406 mm)
Minimum
Field
Constructed
Shroud
Maximum Height of
14 1/2 in. (368 mm)
Open
Top
Only
19 in. (483 mm)
Minimum
Roof
Chase
3 in. (76 mm) air
space from bottom
of shroud to top of
chase
Figure 4 Minimum Dimensions of Shroud & Chase for TS345
25 in. (635 mm
Minimum
Wire
Mesh
Radiation
Shield
Roof
Chase
3 in. (76 mm)
air space from
bottom of shroud
to top of chase.
Maximum Height
of 14 1/2 in.
(368 mm)
28 in. (711 mm)
Minimum
Wire
Mesh
Figure 5 Minimum Dimensions of Shroud & Chase for TR Series Termi-
nation Caps
6" Min.
Above the
Shroud.
Chase
Top
Storm
Collar
Shroud
Leg
(SHROUD)
(TR344/TR11)
Flue
Shroud
Leg
3 in (76 mm)
air space from
bottom of shroud
to top of chase.
28 in. (711 mm)
Minimum
Maximum Height
14 1/2 in. (368 mm)
25 in. (635 mm)
Minimum
(CHASE)
Figure 5 Shroud & TR Series cap with no Radiation Shield