Installation Sheet
23
Majestic • ECHEL36IN-C/STIN-C, ECHEL48IN-C/STIN-C, ECHEL60IN-C, ECHEL72IN-C Installation Manual • 2608-980 Rev. C • 8/19
D. Use of Elbows
Diagonal runs have both vertical and horizontal vent as-
pects when calculating the effects. Use the rise for the
vertical aspect and the run for the horizontal aspect. See
Figure 4.5.
Two 45º elbows may be used in place of one 90º elbow.
On 45º runs, one foot of diagonal is equal to 8-1/2 inch
(216 mm) horizontal run and 8-1/2 inch (216 mm) vertical
run. A length of straight pipe is allowed between two 45º
elbows. See Figure 4.5.
Figure 4.6 shows the vertical and horizontal offsets for
DVP elbows.
Figure 4.5
HORIZONTAL
VERTICAL
RUN
RISE
EFFECTIVE
LENGTH
Y
X
X
X
DVP
Pipe
Effective Length Rise/Run
Inches Millimeters Inches Millimeters
DVP4 4 102 2-3/4 70
DVP6 6 152 4-1/4 108
DVP12 12 305 8-1/2 216
DVP24 24 610 17 432
DVP36 36 914 25-1/2 648
DVP48 48 1219 34 864
DVP6A 3 to 6 76 to 152
2-1/8-4-1/4 54-108
DVP12A 3 to 12 76 to 305
2-1/8-8-1/2 54-216
Vent Type
X
Inches Millimeters
DVP 16-1/4 413
Figure 4.6 Vertical and Horizontal Offset for DVP Elbows
Vent
Type
X Y
Inches Millimeters Inches Millimeters
DVP 4-1/2 114 17 432