Installation Instruction

12
20302381
Designer Series Direct Vent Gas Fireplace


Plan for the installation of your appliance. This includes
determining where the unit is to be installed, the vent con-
guration to be used, framing and nishing details, and
whether any optional accessories (i.e. blower, wall switch,
or remote control) are desired. Consult your local building
code agency to ensure compliance with local codes, includ-
ing permits and inspections.
The following factors should be taken into consideration:
Clearance to side-wall, ceiling, woodwork, and windows.
Minimum clearances to combustibles 

This replace may be installed along a wall, across a
corner, or use an exterior chase. Refer to Figure 8 for
suggested locations.
Location should be out of high trafc areas and away
from furniture and draperies due to heat from appli-
ance.
Y
B
C
Y
X
LU586
Locating unit
D
A
** Island (C) and Room Divider (D) installation is possible as long
as the horizontal portion of the vent system (X) does not exceed
20’ (610cm). See details in Venting Section.
* When you install your replace in (D) Room divider or (E) Flat
on wall corner positions (Y), a minimum of 6” (152mm) clearance
must be maintained from the perpendicular wall and the front side
edge of the replace.
A Flat on wall
B **Island
C *Room divider
D *Flat on wall corner
Y 6” minimum
Figure 8 -
Locate Fireplace
Never obstruct the front opening of the replace.
Do  install in the vicinity where gasoline or other
ammable liquids may be stored.
Vent pipe routing. See Venting section found in this
manual for allowable venting congurations.
These units can be installed in a bedroom. See National
Fuel Gas Code ANSI Z233.1/NFPA 54 (current
edition), the Uniform Mechanical Code — (current edi-
tion), and Local Building Codes for specic installation
requirements.
These units can be installed in a bathroom.