Hardware reference guide
CableFast Cabling
35013379 11/2011 757
NOTE: These are the maximum load current capacities of the 140CFA04000 and
CFG01600 terminal blocks:
1. When using the 140CFA04000 terminal block, the indicated module outputs are
limited to 0.5 A per point, 150 Vac maximum and 0.5 A per point, 150 Vdc
maximum.
2. When using the 140CFG01600 terminal block and either the 140XTS012xx or
140XTS102XX high power cables, the indicated module output ratings are 2 A
per point, 150 Vac maximum, and 2 A per point, 150 Vdc maximum.
3. The 140CFA04000 block does not incorporate an isometric barrier and is not
recommended for use with the 140ATI03000 TC module. Without such a barrier,
temperature readings may vary up to 2 degrees from one end of the block to the
other. If the application can tolerate this temperature error, the block (and module
remote CJC) may be used.
140DDI36400 Not compatible with CableFast. See 140DDI36400 I/O DC Input 24 VDC 6x16 Telefast Input
Module, page 569 for recommended cables
140DDI67300 X
140DDI84100 X
140DDI85300 X XXX
140DDM39000 X
140DDM69000 X (See Note 1)
140DDO15310 X
140DDO35300 XXX
140DDO35301 XXX
140DDO35310 X
140DDO36400 Not compaitble with CableFast. See 140DDO36400 I/O DC Output 24VDC 6x16 Telefast
Output Module, page 632 for recommended cables.
140DDO84300 X (See
Note 2)
140DDO88500 X (See Note 1)
140DRA84000 X (See Note 1)
140DRC83000 X (See Note 1)
140DSI35300 X
140DVO85300 X
X = Valid Selections.