Hardware reference guide

Power Supplies
74
35013379 11/2011
LED Indicator and Description
The following figure shows the CPS11100 (PV01 or greater) LED indicator.
NOTE: For "closed system" installations, connector 140XTS00 500 must be used
(refer to Closed System Installation, page 750 ).
Input Current 0.4 A @ 115 Vac. 0.2 A @ 230 Vac
Inrush Current 10 A @ 115 Vac. 20 A @ 230 Vac
VA Rating 50 VA
Input Power Interruption 1/2 cycle @ full load and minimum rated line voltage /
frequency. No less than 1 second between interruptions.
Fusing (external) 1.5 A slo-blo recommended (Part # 043502515 or
equivalent)
Output to Bus
Voltage 5.1 Vdc
Maximum Current 3 A
Minimum Current 0.3 A
Protection Over Current, Over Voltage
General
Field Wiring Connector
(included)
7 point terminal strip (Part # 043506326)
Internal Power Dissipation 2.0 + 3.0 x I
OUT
= Watts (where I
OUT
is in Amperes)
Operating Mode Standalone
Specifications