24 Vdc Powered Systems for CE Compliance
The following figure shows the 3 A, 24 Vdc powered systems for CE compliance.
3 Schaffner FvN670-3/06 Line Filter (fast on terminals)
Dimensions:
Length: 3.4" (85 mm)
Width: 2.2" (55 mm)
Height: 1.6" (40 mm)
Mounting Holes: 0.2 in (5.3 mm) dia.,
3 in (75 MM) centerline mounted.
Fast on terminals: 0.25 in (6.4 mm)
Install next to the power
supply.
4 N/A N/A Ground Braid
Flat braid 0.5 in (134 mm) with a
maximum length of 4" (100 mm)
N/A
5 Offlex Series
100cy
35005 Line Cord
The maximum length is 8.5" (215 mm)
Third lead (green/yellow) is
not used; terminate the
shield at the power supply
ground terminal.
Callout Vendor (or
equivalent)
Part Number Description Instruction
CAUTION
European compliance
To maintain CE compliance with the European Directive on EMC (89/336/EEC)
and the Low Voltage Directive (73/23/EEC), the 140CPS21100, the
140CRA21120, and the 140CRA21220 must be installed in accordance with these
instructions.
Failure to follow these instructions can result in injury or equipment damage.