Hardware reference guide

Pwr. & Grnding. Guide
734
35013379 11/2011
AC Powered Systems for CE Compliance
The following figure shows the AC powered systems for CE compliance.
CAUTION
European Compliance
To maintain CE compliance with the European Directive on EMC (89/336/EEC),
the 140CPS11100 (PV00 only), 140CPS11400, 140CPS11410, 140CPS12400,
140CRA21110 and the 140CRA21210 power supplies must be installed in
accordance with these instructions.
Failure to follow these instructions can result in injury or equipment damage.
CAUTION
Requirements Compliance
For installations that must meet "Closed System" requirements, as defined in EN
61131-2 (without relying upon an external enclosure), connector models 140 XTS
00100 and 140 XTS 00500 are required. Also, if an external Line Filter is used, it
must be protected by a separate enclosure which meets the "finger safe"
requirements of IEC 529, Class IP20. See Closed System Installation, page 750
Failure to follow these instructions can result in injury or equipment damage.