Hardware reference guide
Power Supplies
35013379 11/2011 71
LED Indicator and Description
The following figure shows the CPS11100 LED indicator.
NOTE: For "Closed System" installations, connector 140XTS00 500 must be used
(refer to Closed System Installation, page 750 ).
Input Voltage Total Harmonic
Distortion
Less than 10% of the fundamental ms value
Input Current 0.4 A @ 115 Vac. 0.2 A @ 230 Vac
Inrush Current 13 A @ 115 Vac. @ 25°C first power up
23 A @ 230 Vac. @ 25° C first power up
VA Rating 50 VA
Input Power Interruption 1/2 cycle @ full load and minimum rated line voltage /
frequency. No less than 1 second between interruptions.
Fusing (external) 1.5 A slo-blo recommended (Part # 043502515 or
equivalent)
Output to Bus
Voltage 5.1 Vdc
Maximum Current 3 A
Minimum Current None required
Protection Over Current, Over Voltage
General
Field Wiring Connector
(included)
7 point terminal strip (Part # 043506326)
Internal Power Dissipation 6 Watts typ.
Operating Mode Standalone
Specifications