Hardware reference guide

I/O Modules
666
35013379 11/2011
Open–Circuit Monitoring
Broken–wire detection OFF current < 0.15 mA
Shunt resistor Recommended 56 kΩ with 24 Vdc external power
supply
Fusing
Internal None
External User discretion
Specifications