Hardware reference guide

I/O Modules
648
35013379 11/2011
140DRC83000 Quantum I/O Relay Output 8x1 Normally Open/Normally Closed
Module
Overview
The Relay Output 8x1 Normally Open/Normally Closed module is used to switch
voltage sources using eight relays with normally open and normally closed contacts.
Specifications
The following table shows the specifications for the DRC83000 RELAY OUT
module.
Specifications
Number of Output Points 8 normally open / normally closed pairs
LEDs Active
1 ... 8 (Green) - Indicates point status
Required Addressing 0.5 word out
Voltage
Working 20 ... 250 Vac
5 ... 30 Vdc
30 ... 150 Vdc (reduced load current)
Maximum Load Current
Each Point 5 A max at 250 Vac, 30 Vdc @ 60° C ambient, resistive load
2 A Tungsten lamp load
3 A @ power factor 0.4
1/4 hp @ 125/250 Vac
Each Point (30 ... 150 Vdc) 300 mA resistive
100 mA (L/R = 10 msec)