The following figure shows the DAO84010 derating chart.
Surge Current Maximum (rms) Per Point
One Cycle 30 A
Two Cycles 20 A
Three Cycles 10 A
Applied DV / DT 400 V/μs
Response
OFF - ON 0.50 of one line cycle max
ON - OFF 0.50 of one line cycle max
Output Protection RC snubber suppression (internal)
Isolation (rms)
Output to Output 1500 Vac for 1 minute
Output to Bus 1780 for 1 minute
Bus Current Required 350 mA
Power Dissipation 1.85 W + 1.1 x Total Module Load Current
External Power Not required for this module
Fusing
Internal None
External Each output point must be fused with an external
fuse. The recommended fuse is a 5 A fuse
(Part # 043502405 or equivalent) or any other fuse
with an I
2
T rating of less than 87.
Specifications