Hardware reference guide
I/O Modules
35013379 11/2011 591
140DAO84000 I/O AC Output 24 ... 230 Vac 16x1 Module
Overview
The AC Output 24 ... 230 Vac 16x1 module switches 24 ... 230 Vac powered loads.
Specifications
The following table shows the specifications for the AC Output 24 ... 230 VAC OUT
module.
Specifications
Number of Output Points 16 isolated
LEDs Active
1 ... 16 (Green) - Indicates point status
Required Addressing 1 word out
Voltage (rms)
Working 20 ... 253 Vac
Absolute Maximum 300 Vac for 10 s
400 Vac for 1 cycle
Frequency 47 ... 63 Hz
ON State Drop / Point 1.5 Vac
Minimum Load Current (rms) 5 mA
Maximum Load Current (rms)
Each Point* 24 to 115 VAC, 4 Amps per output
200 to 230 VAC, 3 Amps per output
Any Four Contiguous Points 4 A max continuous for the sum of the four points
Per Module* 16 A continuous (See the derating chart)
Off State Leakage / Point (max) 2.5 mA @ 230 Vac
2 mA @ 115 Vac
1 mA @ 48 Vac
1 mA @ 24 Vac