Hardware reference guide

System Specifications
35013379 11/2011 55
I/O Modules - Table 3
The following table shows the Quantum I/O modules with operating voltages greater
than 48 Vac or Vdc.
Operating Conditions
The following table shows the Quantum operating conditions.
Gas Resistance in Conformally Coated Modules
The following table shows gas resistance data for conformally coated Quantum
modules.
Fast Transients (IEC 1000-4-4) 2 kV
Damped Oscillatory Transients 2 kV common mode
1 kV differential mode
Surge Withstand Capability (Transients) (IEC 1000-4-5) 2 kV common mode
1 kV differential mode
Temperature 0 ... 60° C (32 ... 140° F), unless specified otherwise
Humidity 0 ... 95 percent RH non-condensing at 60° C
Chemical
Interactions
Enclosures and terminal strips are made of polycarbonates. This material
can be damaged by strong alkalis and various hydrocarbons, esters,
halogens and ketones in combination with heat. Common products
containing these include detergents, PVC products, petroleum products,
pesticides, disinfectants, paint removers, and spray paints.
Altitude 2,000 meters. When the altitude exceeds this, reduce the 60° C maximum
operating temperature by 6° C per 1000 meters of additional elevation.
Vibration 10 ... 57 Hz at 0.075 mm d.a. 57 ... 150 Hz at 1 g
Shock +/-15 g peak, 11 ms, half-sine wave
Mixed Flowing Gas Test, 22 days exposure
Standard Gas Test Requirement Actual Exposure
EIA364-65 Level lll CL
2
(Chlorine) 20 PPB, +/- 5 PPB 20 PPB
NO
2
(Nirtic Oxide) 200 PPB, +/- 50 PPB 1250 PPB
H
2
S (Hydrogen Sulfide) 100 PPB, +/- 20 PPB 100 PPB
SO
2
(Sulfur Oxide) N/A 300 PPB
ISA-S71.04 (GX
Severe)
CL
2
(Chlorine) 10 PPB 20 PPB
NO
2
((Nitric Oxide) 1250 PPB 1250 PPB
H
2
S (Hydrogen Sulfide) 50 PPB 100 PPB
O
2
(Sulfur Oxide) 300 PPB 300 PPB