Hardware reference guide
System Specifications
54
35013379 11/2011
Electrical Specifications
The following table shows the Quantum electrical specifications.
AC/DC Power Supplies
The following table shows the Quantum AC/DC power supplies.
I/O Modules - Table 1
The following table shows the Quantum function I/O modules with operating
voltages less than 24 Vac or Vdc.
I/O Modules - Table 2
The following table shows the Quantum I/O modules with operating voltages
between 24 and 48 Vac or Vdc.
RFI Immunity (IEC 1000-4-3) 80 ...1000 MHz, 10 V/m
Ground Continuity (IEC 1000-4-5) 2 kV shield to ground
Electrostatic Discharge (IEC 1000-4-2) 8 kV air / 4 kV contact
Flammability Wiring Connector: 94V-0 Module Enclosure: 94V-1
Fast Transients (IEC 1000-4-4) 2 kV common mode
Damped Oscillatory Transients 2 kV common mode
1 kV differential mode
Surge Withstand Capability (Transients)
(IEC 1000-4-5)
2 kV common mode
1 kV differential mode
Non Periodic Peak Input Voltage 2.3 times nominal for 1.3 ms (Nominal = DC
average or AC peak)
Fast Transients (IEC 1000-4-4) 0.5 kV common mode
Damped Oscillatory Transients 1 kV common mode
0.5 kV differential mode
Surge Withstand Capability (Transients) (IEC 1000-4-5) 1 kV common mode
0.5 kV differential mode
Fast Transients (IEC 1000-4-4) 1 kV
Damped Oscillatory Transients 2 kV common mode
1 kV differential mode
Surge Withstand Capability (Transients) (IEC 1000-4-5) 1 kV common mode
0.5 kV differential mode