Hardware reference guide
I/O Modules
524
35013379 11/2011
Linear Measuring Ranges
The following table shows the linear measuring ranges for the 140AMM09000
combination Analog module.
4x Registers
The following figure shows the 4X registers.
NOTE: The data format is always 0 ... 4095 decimal (in Modsoft).
Data Format Input Under
Warning
Normal Over
Warning
16-bit
Format
+/- 10 V < 768 768 ... 64,768 > 64,768
+/- 5 V, +/- 20 mA < 16,768 16,768 ... 48,768 > 48,768
0 ... 10 V 0 ... 64,000 > 64,000
0 ... 5 V, 0 ... 20 mA 0 ... 32,000 > 32,000
1 ... 5 V, 4 ... 20 mA < 6,400 6,400 ... 32,000 > 32,000
Voltmeter
Format*
+/- 10 V < -10,000 -10,000 ... 10,000 > 10,000
+/- 5 V < -5,000 -5,000 ... 5,000 > 5,000
0 ... 10 V 0 ... 10,000 > 10,000
0 ... 5 V 0 ... 5,000 > 5,000
1 ... 5 V < 1,000 1,000 ... 5,000 > 5,000
+/- 20mA < -20,000 -20,000 ... 20,000 > 20,000
0 ... 20mA 0 ... 20,000 > 20,000
4 ... 20mA < 4,000 4000 ... 20,000 >20,000
12-bit
Format
+/- 10 V 0 0 ... 4,095 4,095
+/- 5 V, +/- 20 mA 0 0 ... 4,095 4,095
0 ... 10 V 0 ... 4,095 4,095
0 ... 5 V, 0 ... 20 mA 0 ... 4,095 4,095
1 ... 5 V, 4 ... 20 mA 0 0 ... 4,095 4,095