Hardware reference guide

I/O Modules
522
35013379 11/2011
Configuration of the 140AMM09000 Analog Input/Output Module
Overview
This section provides information on configuration of the analog input/output module
140AMM09000.
NOTE: Modsoft V2.2 or above is required to set up your Quantum I/O configuration.
I/O Map Register Assignment
This module requires five contiguous input (3x) registers and two output (4x)
registers.
3X Registers
The following figure shows the 3x registers.
NOTE: The input data format and resolution are selected in Zoom screen. Voltmeter
mode is recommended for bipolar ranges with signed decimal numbers.