Hardware reference guide
I/O Modules
518
35013379 11/2011
NOTE: The output levels of this module are either those generated within the
module based on data inputs from the system, or from the master override inputs on
the field-wiring terminal strip.
NOTE: If module power is lost or the module fails, the master override levels will be
output.
Wiring Diagram
Maximum Settling Time 700 μs to +/- 0.1% of the final value
Update Time 3 ms for all channels
Fault Detection None
Wire Length 400 m max
Bus Current Required 700 mA
Power Dissipation 4.5 W max
External Power Not required for this module
Fusing
Internal None
External An external fuse is required on the master override signal when it
is connected to an external source. The required fuse is 1/16 A or
0.063 A fuse.
Fuse Type: 3AG Fast Acting 1/16 A, 250 V
Fuse Holder: 3AG Fuse Type
The external fuse is not required if master override is connected
to common.
Specifications
WARNING
Possible injury to personnel or equipment
Before removing the connector, ensure that it is safe to have field wiring in an open
circuit condition.
Failure to follow these instructions can result in death, serious injury, or
equipment damage.