Hardware reference guide

I/O Modules
490
35013379 11/2011
140ACI04000 High Density Analog in I/O Module
Overview
The 140ACI04000 is a 16 channel analog input module which accepts mixed current
inputs.
Specifications
The following table shows the specifications for the ACI04000 analog input module.
Specifications
Number of Channels 16 Differential or 16 externally tied single ended
LEDs Active: Indicates Bus communication is present
F: Indicates channel fault.
NOTE: This module produces a fault signal F if any one channel
detects a broken wire condition in the 4 ... 20 mA range.
Required Addressing 17 Words In
Current Input
Linear Measuring Range 0 ... 25 mA, 0 ... 25,000 counts
0 ... 20 mA, 0 ... 20,000 counts
4 ... 20 mA, 0 ...16,000 counts
4 ... 20 mA, 0 ... 4,095 counts
Absolute Maximum Input 30 mA
Input Impedance 250 Ω nominal
Accuracy Error @ 25° C +/- 0.125% of full scale
Linearity (0 to 60° C) +/- 6μA max, 0 ... 25 mA, 0 ... 25,000 counts
+/- 6μA max, 0 ... 20 mA, 0 ... 20,000 counts
+/- 6μA max, 4 ... 20 mA, 0 ... 16,000 counts
+/- 12μA max, 4 ... 20 mA, 0 ... 4,095 counts
Accuracy Drift
w/Temperature
Typical:
Maximum:
+/- 0.0025% of full scale / ° C
+/- 0.005% of full scale / ° C
Common Mode Rejection > -90 dB @ 60Hz
Input Filter Single pole low pass, -3 dB cutoff @ 34 Hz, +/- 25%
Isolation
Field to bus 1780 Vac for 1 minute
Operating Voltage
Channel to Channel 30 Vdc max
Update Time 15ms for all 16 channels
Fault Detection Broken wire in 4 ... 20 mA mode
Bus Current Required 360 mA