Hardware reference guide
I/O Modules
35013379 11/2011 487
NOTE: Calibration is not required for this module.
Wiring Diagram
Isolation
Channel to Bus 1000 Vdc, 3000 Vpp, for 1 minute
Operating Voltage
Channel to Channel 30 Vdc max
Update Time 5 ms for all channels
Fault Detection Broken wire (4 ... 20 mA mode) or under voltage range (1 ... 5 V)
Bus Current Required 240 mA
Power Dissipation 2 W
External Power Not required for this module
Specifications
CAUTION
Possible Equipment Failure
When configured for voltage inputs (no jumper installed between INPUT(+) and
ISENSE terminals), if a broken field wire occurs, readings will be non-zero and not
predictable.
Failure to follow these instructions can result in injury or equipment damage.