Hardware reference guide
Intrinsically Safe Modules
35013379 11/2011 421
Field Wiring
Field wiring to the module should consist of separate shielded, twisted pair wires.
The acceptable field wire gauge should be AWG 30 to AWG 18. Wiring between the
module and the intrinsically safe field device should follow intrinsically safe wiring
practices to avoid the transfer of unsafe levels of energy to the hazardous area.
Fixed Wiring System
The Quantum140AIO33000 Intrinsically Safe Analog Output module is designed
with a fixed wiring system where the field connections are made to a 40-pin, fixed
position, blue terminal strip which is plugged into the module.
Terminal Strip Color and Keying Assignment
The module’s 140XTS33200 field wiring terminal strip is color-coded blue to identify
it as an intrinsically safe connector.
The terminal strip is keyed to prevent the wrong connector from being applied to the
module. The keying assignment is given below.
Voltmeter Monitor Specifications
Range 0.250 ... 1.250 V
Scaling
(Volts) = (mA) x 0.0625
Output Impedance 62.5 W Typical
Wire Length 1 m maximum
Hot Swap Not allowed per intrinsic safety standards
Fusing Internal - not user accessible
Programming Software Modsoft Ver. 2.61or higher
Specifications
Module Class Module Part Number Module Coding Terminal Strip Coding
Intrinsically Safe 140AIO33000 CEF ABD