Hardware reference guide

Intelligent/Special Purpose
35013379 11/2011 371
The following table shows the operational specifications for discrete inputs.
The following table shows the operational specifications for discrete outputs.
The following table shows the operational specifications for analog input.
The following table shows the operational specifications for analog output.
Discrete Inputs
Number 7
Scan Time 1.5 ms
Isolation 500 V to system bus
Discrete Outputs
Number 3
Update Time 10 ms max
Isolation 500 V to system bus
Reset State 0 V, nominal
On State 24 V, nominal
Output Type Totem pole (sink/source)
Protection Short circuit, overvoltage
Fault Overcurrent detected
Analog Input
Number 1
Scan Time 15 ms
Data User configurable
Range +/- 10 V
Accuracy +/- 100 mV, plus offset
Analog Output
Number 1
Scan Time 20 ms
Data User configurable
Range +/- 10 V
Accuracy +/- 50 mV, plus offset