Hardware reference guide
Intelligent/Special Purpose
366
35013379 11/2011
Specifications
The following table shows the specifications for the HLI34000 high speed interrupt
module.
Specifications
Number of Input Points 16 isolated points
LEDs Active 1 ... 16 (Green) - Indicates point status
Required Addressing 1 Word In
Operating Voltages and Currents
ON (voltage) 15 ... 30 Vdc
OFF (voltage) -3 ... +5 Vdc
ON (current) 2.0 ... 8.0 mA
OFF (current) 0 ... 0.5 mA
Absolute Maximum Input
Continuous 30 Vdc
Response
OFF - ON 30 μs (max)
ON - OFF 130 μs (max)
Input Protection 30 Vdc reverse polarity
Isolation
Point to Point 500 Vac rms for 1 minute
Point to Bus 1780 Vac rms for 1 minute
Fault Detection None
Bus Current Required 400 mA
Power Dissipation 2.0 W + 0.30 W x the number of points on
External Power Not required for this module
Fusing
Internal None
External User discretion