Hardware reference guide
Intelligent/Special Purpose
338
35013379 11/2011
Load Values
The following table shows the load values.
NOTE: Command echoes are the same as described in the Pulse Input Count
Up/Down examples.
Read Rate Sample
The following table shows a read rate sample.
When this command is issued, the input pulse counter content is retrieved. The 3X
register content is the count over the time period selected in the Load Values
registers 4X + 1 and 4X + 2. The 3X response to the Read-Rate Sample command
in register 40301 is as follows.
Response to Read Rate Sample Command
The following table shows the responses to the read rate sample command.
400201 0243 LOAD VALUES command, disable Counter 2, preset and enable
Counter 1
400202 XXXX Counter 1 Rate Sample Time in milliseconds
400203 0000 Counter 2 Rate Sample Time in milliseconds (Not used in this
example)
400204 0000 Not used by this command
400205 0000
400206 0000
40030 0400 READ INPUT COUNTER command
400302 0000
Not used by this command
400303 0000
400304 0000
400305 0000
400306 0000
Register Value Description
300001 0400 Command echo
300002 XXXX Counter 1 Input rate low word
300003 XXXX Counter 1 Input rate high word: this register is a multiplier. As an
example: 30002 has a value of 324 and 30003 a value of 3.The
total count is (65,536 x 3) + 324 = 196,932
300004 0000 Counter 2 is disabled
300005 0000 Counter 2 is disabled
300006 0X00 X is the field power indicator