3x Register Content
Reset of Latched Outputs
If register 400103 in the Module Configuration Table has been set to 4200, Output
1A would have been latched on at setpoint and Output 1B latched on at maximum
count. Wiring Diagrams 2 and 4 show how the encoder Z outputs could be used to
reset the latched outputs. The minimum pulse width to reset outputs is 1 μs.
Register Value Description
300001 0300 Command echo
300002 XXXX Current input count
300003 0000 Zeros as the count will not exceed 100. For counts above 65,536, this
register is a multiplier. As an example: 30002 has a value of 324 and
30003 a value of 3.The total count is (65,536 x 3) + 324 = 196,932
300004 0000 Counter 2 is disabled
300005 0000 Counter 2 is disabled
300006 0X00 X is the field power indicator