Hardware reference guide

Intelligent/Special Purpose
334
35013379 11/2011
Zeros in the 4X registers also mean no change. Setpoint, maximum count and
assert time can only be set to zero using the Modzoom screens. When the registers
in this example are echoed, zeros will appear but the actual content in the module
will be unchanged from previous values. In this example, Counter 2 is disabled and
its outputs and timed assert have not been selected. Registers 400204 - 6 have no
meaning.
After the module executes the Configure and Load Value’s commands, they are
echoed in the I/O mapped 3X registers except for the command register’s low 8 bits.
Command execution time by the module is 1 ms. Actual time between the 4X
register block move and the echo response display in the 3X registers is dependent
on User Logic and hardware configuration. An echo of the Configuration command
registers would appear as follows:
Response for Configuration Command
The following table shows the echo response for the configuration command.
Read Input Counter Command
The following table shows the read input registers.
When this command is issued, the content of the input pulse counter is retrieved.
The 3X register content would appear as shown in the following table.
Register Value
300001 0100
300002 0000
300003 3100
300004 0000
300005 0000
300006 0000
40301 0300 READ INPUT COUNTER command
40302 0000
Not used by this command
40303 0000
40304 0000
40305 0000
40306 0000