Hardware reference guide
Intelligent/Special Purpose
35013379 11/2011 333
See 140EHC20200 High Speed Counter Module, page 346 for counter timing
diagrams illustrating output on times.
The following table shows the I/O Map register assignments.
In this example, block moves are used to load the operating parameters into the
module. This requires pre-defined tables be established. Register values are in HEX
format.
Module Configuration
The following table shows the module configurations.
Load Values
The following table shows the load values.
Module Input Ref Output Ref Description
140EHC20200 300001-300006 400001-400006 EHC20200 High Speed
400101 0140 CONFIGURE command, Disable Counter 2
400102 0000 Pulse input, two 16 bit counters, output assert on Rate
Sample OFF, disable outputs at bus communication loss
400103 3100 Output 1A on at setpoint, Output 1B on at maximum count +1
Output 2A and 2B are disabled
400104 0000
Not used by this command
400105 0000
400106 0000
400201 0243 LOAD VALUES command, disable Counter 2, preset and enable
Counter 1
400202 0064 Counter 1 maximum count, count after which Output 1B turns on
400203 0032 Counter 1 setpoint, count when Output 1A turns on
400204 0000 Counter 2 maximum count (not used in this example)
400205 0000 Counter 2 setpoint (not used in this example)
400206 0000 Output Assert Time (Not used in this example, one output only, if
used)