Hardware reference guide
Intelligent/Special Purpose
332
35013379 11/2011
Command 4 Response Format
The following figures show the counters for 3X through 3X+5 for command 4.
I/O Map Status Byte
The most significant bit in the I/O Map status byte is used for the 140EHC20200
High Speed Counter Module. The following figure shows the map status byte
register.
Using I/O Mapped Registers to Operate the High Speed Counter
COUNT UP Example
Field connections for this example are illustrated in the EHC202 wiring diagrams 1–
4 in this section. The maximum allowable Vref value is 30 Vdc. Input pulse on-off
threshold levels for the 5 ... 24 Vdc Vref range are listed in the module specification
table. The minimum differential input is 1.8 V.
The following user logic:
z Configures the module to count up from zero.
z Turns an output on for one count at a setpoint value of 50.
z Continues counting to 100.
z Rolls over to zero and turn on a second output for one count.
z Repeats the operation.