Hardware reference guide

Intelligent/Special Purpose
35013379 11/2011 325
The following figure shows the 4x+1 output register for command 1 (4X+1).
The following figure shows the 4x+2 output register for command 1.
CAUTION
Module disable possibility
The Output ON time specified in the Command 2 registers may be used by only
one of the four outputs. When more than one output is set to mode 5 or 6, the
module firmware will operate the first one encountered, and disable the other
outputs set to modes 5 or 6.