Hardware reference guide

Ethernet Modules
35013379 11/2011 305
Run LED Status
The following table lists each available state of the Run LED indicator and provides
diagnostic information for that state
Key Features
The key features of the 140 NOE 771 (-00, -01, -10, -11) models are listed below:
Indicator State Status
On (steady) Normal operation: The NOE module is ready for network
communication.
Number of flashes in sequence
one Not used
two Not used
three No Link: the network cable is not connected or is defective.
four Duplicate IP address: The module will be set to its default IP address.
five No IP address: The module is attempting to obtain an IP address from
a BOOTP server. Module is set to default IP address.
six Invalid IP configuration. (Likely cause: Default gateway is not on the
same subnet mask. Module is set to default IP address.
seven No valid executive NOE present
-00 -01 -10 -11
HTTP Server X X X X
FTP Server X X X X
Flash File System X X X X
BOOTP Client X X X X
BOOTP Server X X X X
SNMP V2 Agent X X X X
MODBUS Messaging X X X X
I/O Scanner X X X
Hot Standby X In Version 2.0 X In Version 2.0
Global Data - Publish / Subscribe X X
Bandwidth Monitoring X X
Faulty Device Replacement (DHCP Server) X X
Enhanced Web Diagnostics X X
Schneider Private MIB X X
FactoryCast Application X X
User Programmable Web Pages X X