Hardware reference guide
Modbus Plus NOM
286
35013379 11/2011
Network Status
The information about the condition of the network is presented in the form of
Network Status. This information indicates the loss of connection (the first break in
the self healing ring) and is similar to the way existing 140NOM21200 reports the
loss of redundant cable.
The break of the fiber cable will be detected by the module not receiving the signal
from the side where the cable is broken and will be reported as a Cable B Framing
error by MBPSTAT. This condition will also activate the FRNGoff LED on the front
of the module.
Recommended Materials for Fiber Optic Links
Modicon does not manufacture fiber optic products such as cables, connectors, or
special tools. However, we have experience with third party suppliers of materials
and can give some guidelines on what will work with our products.
Connectors
The following table shows the connector types
NOTE: All connectors must have a short boot for strain relief.
Termination Kits
The following table shows the termination kits.
Connector Type Part Number Operating Temperature
ST Bayonet (Epoxy) 3M 6105 -40 ... +80° C
ST Bayonet (Hot Melt) 3M 6100 -40 ... +60° C
ST Bayonet (Epoxy) AMP 501380-5 Series -30 ... +70° C
ST Bayonet (Epoxy) AMP 503415-1 Series -20 ... +75° C
Light_Crimp ST Style AMP 503453-1 Series -20 ... + 60° C
Mechanical Line Splice (one
size fits all)
3M 2529 Fiberlok1 II -40 ... +80° C
Kit Type Part Number Description
Bayonet ST (Epoxy) AMP 503746-1 For all epoxy type ST style
Light_Crimp XTC AMP 50330-2 For all Light_Crimp
Mechanical Line Splice 3M 2530 Fiber Splice Prep Kit, complete with
cleaving tool
3M Hot Melt 3M 05-00185
3M 05-00187
110 V Termination Kit
220 V Termination Kit