Hardware reference guide
Networking
250
35013379 11/2011
Diagnostic Relay
A normally closed relay contact, rated at 220 Vac 6 A or 30 Vdc 5 A, is available on
the terminals of the diagnostic relay port via its connector.
The following figure shows the 2 terminals of the diagnostic relay connector:
The contacts of the relay are open whenever an error is detected (internal or
external), and the Fault LED is ON. In fact the status of the diagnostic relay provides
an electric information when the Fault LED status provides a visual status when an
error is detected (internal or external).
Optical Transmitter Specifications
Optical Power (Measured
with 1 m test fiber)
–13.0...–20.0 dBm average power in 50/125 µm fiber cable
–10.0...–16 dBm average power in 62.5/125 µm fiber cable
–4.0...–10.5 dBm average power in 100/140 µm fiber cable
Rise/Fall Time 20 nsec or better
Silence (OFF Leakage) –43 dBm
Optical Receiver Specifications
Receiver Sensitivity –30 dBm average power
Dynamic Range 20 dB
Detected Silence –36 dBm
Reliability
MTBF 1,300,000 hours (minimum) @ 30 ° C, assuming fixed ground
and component stress within maximum specifications.
NOTICE
INOPERABLE EQUIPMENT
Do not tighten the right-angle F adapter beyond specified torque.
Failure to follow these instructions can result in equipment damage.
Specifications