Hardware reference guide

DIO
35013379 11/2011 229
Input Current 0.4 A @ 115 Vac. 0.2 A @ 230 Vac
Inrush Current 10 A @ 115 Vac. 20 A @ 230 Vac
VA Rating 50 VA
Input Power Interruption 1/2 cycle at full load and minimum rated line voltage /
frequency. No less than 1 second between
interruptions.
Fusing (external) 1.5 A (Part #043502515 or equivalent)
Operating Mode Standalone or not powered (see Power and Grounding
Guidelines, page 725).
Output to Bus
Voltage 5.1 Vdc
Current 3 A
Minimum Load 0 A
Protection Over Current, Over Voltage
Communication
Modbus Plus 1 port (single cable); 2 ports (dual cable)
General
Specifications I/O Type: Quantum
Modules/Drop: Depends on bus current loading and
word count
Words: 30 In / 32 Out. (Two additional input
words are reserved for drop status.)
Diagnostics Power Up Runtime
RAM Data/Address
Executive Checksum
Field Wiring Connector 7 point terminal strip (Part # 043506326)
Internal Power Dissipation 2.0 V + 3.0 V x I
BUS
= Watts (where IBUS is in Amperes)
Specifications