10. Once the engine starts it will immediately begin speeding up to a constant 1800 rpm. On units with
isochronous engine governing, the engine may hunt or change speeds until operating temperature is
reached. After a few minutes of operation, the engine will be warmed up and the LCD window will show
engine and generator operating parameters. Temperature will be shown as “0” until the engine tempera-
ture is approximately 100° F.
11. Once the generator is at normal operating temperature, check the generator for excessive noise or
vibration and any coolant, oil or fuel leaks before applying any loads.
12. Check that the AC output voltage is correct. The output voltage can be fine adjusted by using the fine
voltage adjustment screw (rheostat), as described on page 15.
13. Check that the frequency (Hz) is correct. With no loads connected to the generator, the frequency
should read approximately 60-62 Hz, depending on the type of engine governing used.
14. If all wiring connections have been made correctly, switch the main circuit breaker to the “ON / I”
position and then add any loads attached to the convenience outlets by switching the respective circuit
breaker to the “ON / I” position. You will notice a slight change in engine sound when a load is applied
to the unit.
“AUTO” (REMOTE) STARTING OF THE LIGHT TOWER
The “AUTO” button is used when the generator is started from a location other than the control panel and by using
a dry-contact closure remote start switch (transfer switch). “AUTO” (remote start) is the normal setting when the
generator is being used as a standby power supply. Before putting the generator in the “AUTO” mode, review the
Pre-Start Check List and Manual Starting of the Generator sections beginning on page 28. Also follow all safety
warnings and information on isolating the generator with a transfer switch if the unit is to be used as a standby
power supply, as described on pages 23 and 24. Then continue with the steps described below:
1. Perform a manual start of the generator at least once to verify that the engine is operating correctly.
2. If a check of the remote start circuit is desired, remove the wires from the remote start terminal block.
Press the “AUTO” button, the Liquid Crystal Display (LCD) window should highlight “AUTO” in the
upper left corner. Attach a jumper wire (minimum 16 gauge) across the two terminals on the remote
start terminal block. This applies a ground to the Magnum Digital Controller (MDC) to close the starting
circuit contacts. The engine should crank, start and run.
3. Remove the jumper wire from the remote start terminal block and the engine will stop. Reconnect any
necessary wires from the remote start switch (transfer switch) to the remote start terminal block.
4. Confirm unit is in “AUTO” mode. The LCD window should have “AUT” highlighted in the upper left
corner.
5. Close (set to “ON / I”) the main circuit breaker.
6. Secure the generator by closing and locking all access doors.
7. The generator is now ready for remote starting.
30