Technical information

Enrange MHR Instruction Manual
August 2014
Page 55 of 57
Alarm
Number
Alarm
Text
Cause of alarm Effect of alarm Recovery Action
62
S62. OUT
15 -VB
SHORT
When the output is
supposed to be at
+VBat, a voltage of
2V or less was seen
on the output. The
output was shut off to
prevent damage to
the hardware.
Output is shut off and will
not operate until the cause
is fixed and power to the
system is cycled
Determine the cause of the
short, fix the cause, and power
cycle the system
63
S63. OUT
16 -VB
SHORT
When the output is
supposed to be at
+VBat, a voltage of
2V or less was seen
on the output. The
output was shut off to
prevent damage to
the hardware.
Output is shut off and will
not operate until the cause
is fixed and power to the
system is cycled
Determine the cause of the
short, fix the cause, and power
cycle the system