Spec Sheet
GD-6 Specifications
• Power: 3 W (max) from 12 to 24 VAC or 12 to 48 VDC
• Current @ 24 VDC: 75 mA in alarm, 50 mA fan relay on and 23 mA stand by
• Shipping Weight: 1 pound (0.45 kg)
• Size: 4 1/2 x 4 x 2 1/8 in. (11.4 X 10.2 X 5.4 cm)
• Color: Dark gray
• Connections: plugs/terminals
• Mounting box: (not included) 4x4 electric
• Fan relay: 5 A, 240 VAC, pilot duty, SPDT, latching or non-latching
• Fan relay actuation: selectable at OFF, 3, 4, 5, 6, 7, 8, 9,
10 (default), 11, 12, 13, 14, 15, 16, 17, 18, 19, 20% LEL
• Fan Delay Settings of 0, 1, 3 (default), 5 and 10 minutes
• Fan Minimum Runtime settings are OFF (default), 3, 5, 10 or 15 minutes
• Alarm relay: 0.5A 120 V, 60 VA
• Alarm relay actuation: selectable N.O. default or N.C.
GD-6 Rear View
• Alarm relay settings: OFF, 5, 10, 15, 20 (default), 25% LEL
• Current Loop, 4-20 mA for 0-50% LEL
• Operating Environment: 0°F to 125° F (-18°C to 52°C),10 to 90% RH
Location
A GD-6 is usually located in areas where there is potential for gas leaks; where there are gas appliances, areas
through which gas pipes pass, where batteries are being stored or charged, etc. DO NOT mount the GD-6 in a
corner. DO NOT mount the GD-6 where the normal ambient temperature is below 0°F or exceeds 125°F (-18°C
to 52°C). If the target gas is lighter than air; natural gas (Methane) or Hydrogen (H2), mount the GD-6 high on a
wall or column about one foot down from the ceiling. If the target gas is heavier than air; propane (LP), mount the
GD-6 low on a wall or column one foot above the floor. Use the same spacing as for smoke detectors, 30 foot
centers, 900 square feet per detector.
TYPICAL CONNECTION OF GD-6
TYPICAL COVERAGE 900 SQUARE FEET
Made in the U.S.A. with US and imported materials
© Aerionics 2014. All rights reserved.
Macurco is a trademark of Aerionics, Inc.
Made in the USA
N.C.
N.O.
AC or DC
No Polarity
A
B
N.O.
COM
N.C.
ALARM
RELAY
POWER
12 or 24 V
SPDT fan
RELAY
GD-6
4-20 mA
Loop
+
-
24V Gas
Valve
Wall
The Gas Valve mounts outside.
Gas
line
from
tank
Gas line to
appliances
auxiliary functions
such as dialers.
N.O. or N.C.
initiating circuit
24V power
battery backed up
Alarm Control Panel