User Manual

Table Of Contents
Macurco CX-xx Manual (Rev-1.0) Eng
REV 1.1 [34-2900-0512-0 ] 21 | Page
Clean AirThe CX-xx will flash between the current concentration of CO ppm and the current concentration of NO
2
ppm. The CO reading will start with a “C” and the NO
2
reading will start with an “n”.
Fan Relay LevelWhen either the CO or NO
2
concentration reaches the Fan Relay setting and the Fan Run Delay
“Frd” period has elapsed, the display will flash between “FAn” and the current concentration of gases. The
sequence of display when the Fan Relay is activated is: “Fan”, CO (“CXXX) reading, NO
2
reading (“n Y.Y”).
Alarm Relay LevelWhen either the CO or NO
2
concentration reaches the Alarm Relay setting, the display will flash
between “ALr” and the current concentration of gases. The sequence of display when the Alarm Relay is activated is:
ALr, CO Reading (CXXX), NO
2
reading (n Y.Y).The buzzer will sound indicating “Alarm” if the buzzer is turned
“On”.
TroubleWhen the device is in a trouble state, the display will display the “t” Error code (t001 for example) and the
Alarm Relay will activate. If the Trouble Fan Setting is enabled, the Fan Relay will activate. See Section 5.1.2 Trouble
Codes and Section 4.5.14 Select Trouble Fan Setting “tFS”
NOTE: Trouble states related to the CO and NO
2
sensors are represented by different “t” Error codes. So, if an error
exists for the CO or NO
2
sensor only, the display will alternate between the trouble code for the sensor in the
trouble state and the gas reading for the sensor in the normal state.
Calibration DueWhen the Calibration Period functionality is enabled and the detector is within 1 month of the
calibration period, the Calibration Due message will be displayed. Calibration Due is indicated by CdUE(for CO
Sensor) and ndUE(for NO
2
sensor). When both CO and NO
2
sensors are in Calibration Due, the display sequence
will be CdUE, CO reading, ndUE, NO
2
reading.
Calibration Due is resolved only with a successful field calibration.
NOTE: If a Fan or Alarm Relay is activated during Calibration Due, ‘Fan’ or ‘ALr’ will be appended at the end of the
display sequence for calibration due.
4.3 Display turned “Off”
With the display (“dSP”) setting turned OFF”, the detector will operate as follows:
Clean Air –The display does not show the CO or NO
2
concentration. Only the Power indicator light on will be on.
Fan Relay LevelWhen the CO or NO
2
concentration reaches the Fan Relay setting and the Fan Run Delay “Frd”
period has elapsed, the display will continuously show “FAn”.
Alarm Relay LevelThe display does not show the CO or NO
2
concentration but will show “ALr” when the Alarm
relay is activated. The buzzer will sound indicating “Alarm” if the buzzer is turned “On”.
TroubleWhen the device is in a trouble state, the display will display the “t” Error code (t001 for example) and the
Alarm Relay will activate. If the Trouble Fan Setting is enabled, the Fan relay will switch activating the relay. See
Section 5.1.2 Trouble Codes and Section 4.5.14 Select Trouble Fan Setting “tFS”.
Calibration DueWhen the Calibration Period functionality is enabled and the detector is within 1 month of the
calibration period, the Calibration Due message will be displayed. Calibration Due is indicated by CdUE(for CO
Sensor) and ndUE(for NO
2
sensor). When both CO and NO
2
sensor are in Calibration Due, the display sequence
will be CdUE, ndUE”.