Spec Sheet

Specifications
4 1/2 x 4 x 2 1/8 in. (11.4 X 10.2 X 5.4 cm)
1 pound (0.45 kg)
6-Series
Power: 3 W (max) from 12 to 24 VAC or
12 to 32 VDC :Current @ 24 VDC: 75 mA in
alarm, 50 mA fan relay on and 23 mA stand by
12-Series
Power: 100-240 VAC (50 to 60 HZ)
Current: 1.0 A MAX
LED (can turn on/off)
Display
Analog 4-20mA, with MRS-485 Adapter
Digital Modbus
Current Loop
4” x 4” electrical box
Mounting
5A Fan Relay & 0.5A Alarm Relay
User Adjustable Settings
Relays
ETL Listed
*See detector manual for additional certifications
Certifications
Two Year Limited Warranty
Warranty
Voltage/Current
Weight
10-90% RH NonCondensing
Ambient Humidity
0°F to 125°F (-18°C to 52°C)
CD-6/12H 32°F to 122°F (0°C to 50°C)
Operating Temperature
Size
Commercial Series
Macurco
TM
Building & Home Solutions
Building & Home Solutions
© Aerionics 2020. All rights reserved. Macurco is a trademark of Aerionics, Inc.
Macurco Gas Detection
3601 N St. Paul Ave,
Sioux Falls, SD 57104
Website: www.macurco.com
Phone: 1-877-367-7891
Email: info@macurco.com
9/2020
Since 1972 Macurco has been providing gas detection solutions for various
applications. Macurco provides the highest quality gas detection solutions to
customers worldwide.
Model Number
Range
(Units)
Low Level Alarm
Adjustable
(Default)
High Level Alarm
Adjustable
(Default)
Expected
Sensor Life
Recommended
Coverage Area
Gas Type
CM-6 | CM-12 Carbon Monoxide (CO) 0-200 PPM 10 Years 5,000 sq. ft.
5,000 sq. ft.
900 sq. ft.
900 sq. ft.
900 sq. ft.
5,000 sq. ft.
5 Years
2 Years**
2 Years**
2 Years**
0, 15, 25, 35, 50 or 100 PPM
0, 3, 4, 5, 6, 7, 8, 9, 10, 11,
12, 13, 14, 15, 16, 17, 18, 19, 20% LEL
0, 0.5, 0.7, 1.0, 1.2, 1.5, 1.7, 2.0, 2.2, 2.5, 2.7,
3.0, 3.2, 3.5, 3.7, 4.0, 4.2, 4.5, 4.7, 5.0 PPM
0, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14, 15,
16, 17, 18, 19, 20 PPM
0, 15, 20, 25, 30, 35, 40, 45, 50, 55, 60, 65,
70, or 75 PPM
0, 25, 30, 35, 40, 45, 50, 55, 60, 65, 70, 75,
80, 85, 90, 95 or 100 PPM
0, 50, 100, 150 or 200 PPM
OFF, 5, 10, 15, 20, 25% LEL
0-20 PPM, (5 PPM default)
0, 5, 10, 15, 20, 25, 30, 35, 40, 45, 50 PPM
0-50% LEL
0-20 PPM
0-50 PPM
0-100 PPM
Propane (LP) Methane (NG) Hydrogen (H
2
)
Nitrogen Dioxide (NO
2
)
Hydrogen Sulfide (H
2
S)
Ammonia (NH
3
)
900 sq. ft.2 Years**
0, 18, 18.1… , 20.2, 20.3, 20.4 &
20.5% v/v & high 23.5 % v/v (preset)
0, 18.5, 19, 19.5, 20, 20.5 and
high 23.5 % v/v (preset)
0-25 % V/V
Oxygen (O
2
)
900 sq. ft.7 Years
1000 PPM 1000 PPM
0-1,000 PPM
Refrigerant
(R-22, R-134A, R-404A, R-407C, R-410A)
900 - 5000 sq. ft.
15 Years
0, 600, 700, 800, 900, 1000,1100...
2000... to 5000 PPM
0, 900, 1000, 1100...4000 ... to 5000 PPM
0-5,000 PPM
Carbon Dioxide (CO
2
)
GD-6 | GD-12
CX-6 | CX-12
TX-6-ND | TX-12-ND
TX-6-HS | TX-12-HS
TX-6-AM | TX-12-AM
OX-6 | OX-12
RD-6 | RD-12
CD-6H | CD-12H(Auto Cal)
CD-6MC | CD-12MC(Manual Cal)
ISO 9001:2015
ISO 9001:2015
CERTIFIED
Name Model Number
Accessories
Control Panels DVP-120, DVP-120M, DVP-120B
MRS-485Addressable Adapter
Horn and Strobe (5 color options) HS-A, HS-B, HS-R, HS-G, HS-C
DMK-1Duct Mount Kit
Weatherproof Housing Kit WHK-1
PS-24Plug in 24VDC Transformer
Based on Gas TypeCalibration Kits
Weatherproof Housing Kit
(Detector sold separately)
Calibration Kits
Horn and Strobe
Control Panels
Addressable Adapter
** Replaceable Sensor
Carbon Monoxide (CO) & Nitrogen Dioxide (NO
2
)
2 Years**
Refer to CM-6 (CO) & TX-6-ND (NO
2
) Refer to CM-6 (CO) & TX-6-ND (NO
2
)
(CO) 0-200 PPM
(NO
2
) 0-20 PPM