User Instructions
16 
e.  The 4-20mA output will then ramp up from 4 to 16 mA over the next 130 seconds of the test, so if the 
circuit is wired in the normal manner, the control panel or building automation system should respond. 
f.  At the end of the test cycle, the light will turn green and be on steady (Normal Operation), the fan & 
alarm relay will be in standby mode and the 4-20 mA output will return to 4 mA (in clean air). 
8.  When testing is completed reassemble the unit or units. 
Manual Operation Test 
This option gives the user the opportunity to manually initiate an individual test for each relay, the analog output and the sensor 
response to gas. From normal operation mode press the Next button 3 times to get to the Test Mode (tSt). Press the Enter button once 
to get into the Test Menu. Press the Next button to scroll through the four test options and press Enter to initiate the selected test. Note 
that if the relay or 4–20 mA output has been disabled, the test selection will not be displayed in the test menu. 
Art - Alarm Relay Test, 10 seconds 
Frt - Fan Relay Test, 60 seconds 
42t - 420 loop test, 25 seconds 
gtS - Gas Test, 3 minutes (no output to the panel during the gas test) 
The display will flash during the test, or in the case of the gas test, the gas level will alternate with gtS. Once the test is complete, the 
display will return to steady display. To exit the test menu, press the Next button until “End” is displayed then, press Enter to return to 
normal mode.  
Carbon Monoxide Gas Test 
The following steps must be performed when conducting a calibration or calibration verification test (bump test) to ensure proper 
performance of the monitor. Failure to do so may adversely affect product performance and result in sickness or death. 
  When performing a calibration or calibration verification test (bump test) only use certified calibration gas at the 
required concentration level. Do not calibrate with expired calibration gas. 
  If the instrument cannot be calibrated, do not use until the reason can be determined and corrected. 
  Do not cover or obstruct display or visual alarm cover. 
  Ensure sensor inlets are unobstructed and is free of debris 
General 
A Field Calibration Kit, CM6-FCK, is needed to complete a CO gas test. These are available through your local representative or from 
Macurco. 
Contents of the FCK 
  CM6-FCK: (2) Gas Cylinders, (1) 17L 50ppm carbon monoxide (CO) in air and (1) 17L 200 ppm carbon monoxide (CO) in air 
  Gas regulator with about two feet of plastic tubing 
  Humidifier 
  CM-6-CH calibration hood 